Management module is over recommended temperature.
Explanation
The advanced management module has exceeded the recommended temperature threshold.
Severity
Warning
Alert Category
Chassis/System Management (Warning)
-
mmTrapChassisN
Log Source
SERVPROC
Automatically notify service
No
Recoverable
Yes
Chassis LED
Error, Temperature
Alarm Panel LED (BC T and BC HT)
Minor
User response
Perform these steps:
- Check the event log for other over temperature events and resolve them.
- Check the room ambient temperature to ensure that it is within the operating specifications for the chassis.
- Make sure that all fan/blower modules are running. Replace fan modules if necessary.
- Make sure that a device or filler is installed in each bay in the front and rear of the chassis,
and make sure that there is nothing covering the bays. Any missing components can cause a major reduction in airflow for the blade server.
- Check the IBM Support Web page for any service bulletins that might be related to this problem.