Explanation
The temperature for the specified CPU in the specified blade server is over recommended threshold.
Severity
Warning
Alert Category
Blades (Warning)
-
mmTrapBladeN
Log Source
Blade_##
Automatically notify service
No
Recoverable
Yes
Alarm Panel LED (BC T and BC HT)
Minor
User response
Perform these steps:
- Check the room ambient temperature to ensure that it is within the operating specifications for the chassis.
- Make sure that all fan/blower modules are running. Replace fan modules if necessary.
- Make sure that a device or filler is installed in each bay in the front and rear of the chassis, and make sure that there is nothing covering the bays. Any missing components can cause a major reduction in airflow for the blade server.
- Make sure that there is nothing covering the media tray (that will disrupt the airflow to the ambient temperature sensor).