0x0681C482
System shutoff due to DASD Option temperature.

Explanation

The service processor on the specified blade server has shut down because the Direct Access Storage Device (DASD) has reached or exceeded the over-temperature threshold.

Severity

Error

Alert Category

Blades (Critical) - mmTrapBladeC

Log Source

SERVPROC

Automatically notify service

No

Recoverable

Yes

Alarm Panel LED (BC T and BC HT)

Critical

User response

Perform these steps:
  1. Check the room ambient temperature to ensure that it is within the operating specifications for the chassis.
  2. Make sure that all fan/blower modules are running. Replace fan modules if necessary.
  3. Make sure that a device or filler is installed in each bay in the front and rear of the chassis, and make sure that there is nothing covering the bays. Any missing components can cause a major reduction in airflow for the blade server.