0x0F00C008
Blade 08 not allowed to power on; constrained by power budget.

Explanation

While the specified blade server is being powered on, the management module has detected that there is no longer enough power capacity in the power budget to allow the blade server to continue powering on.

Severity

Warning

Alert Category

Chassis/System Management (Warning) - mmTrapChassisN

Log Source

SERVPROC

Automatically notify service

No

Recoverable

Yes

Chassis LED

Error

Alarm Panel LED (BC T and BC HT)

Minor

User response

Perform these steps:
  1. Select a different power management policy to increase the power budget.
  2. Add additional power modules to increase power capacity.
  3. Shut down other devices in the chassis.